The International Building Code is anything but easy to read, which makes sifting through section after section of code requirements a daunting and confusing task. We hope this “condensed” section on the requirements for electromagnetic locks will help ease the headache of code reading.
IBC 1008.1.4.4 Access-Controlled Egress Doors
- Allowed in use groups – A, B, E, I-2, M, R-1, and R-2 (click here for a comprehensive listing of building use groups)
- Applies to doors in a means of egress and entrance doors to tenant spaces
- Means of egress defined: a continuous and unobstructed way of travel from any point within a building/structure to a public way; consisting of three separate parts: the exit access, the exit, and the exit discharge (in an exit path)
- A sensor must be mounted on the egress side to detect an occupant approaching the doors
- Doors must unlock upon signal from the sensor or loss of power to the sensor
- Loss of power to the lock must unlock doors
- A manual (push button) unlocking device shall result in direct interruption of power to the lock – the device must be independent of the access control system electronics
- When the push button is actuated, the doors must remain unlocked for a minimum of 30 seconds
- The push button must include signage stating “push to Exit”
- The push button must be located 40-48” vertically above the floor and within 5’ of the doors
- Ready access must be provided to the push button
- If the building has a fire alarm/sprinkler system/fire detection system, activation of the system must automatically unlock the doors
- Doors must remain unlocked until the system has been reset
- Entrance doors with occupancy in groups A, B, E, or M shall not be secured from the egress side during periods that the building is open to the general public
IBC 1008.1.9.8 Electromagnetic Locks on Egress Doors
- Allowed in use groups – A, B, E, M, R-1, and R-2 (click here for a comprehensive listing of building use groups)
- Applies to doors in a means of egress and doors to tenant spaces
- Door must be equipped with listed hardware mounted on the door leaf
- Incorporates a built-in switch to directly release the electromagnetic lock and unlock the door immediately
- The release device must have an obvious method of operation
- The release device must be readily operated with one hand under all lighting conditions
- Loss of power to the listed hardware must automatically unlock the door